![]() ![]() ![]() ![]() Dimensions are shown for reference
only.
RADIUS POWER
www.radiuspower.com
Specifications are subject to change. Standard & Custom Products PH 714-289-0055
FAX 714-289-2149
Specifications
Operating Frequency: DC - 60Hz
Operating Voltage: 480V +10%
Ambient Temperature: 50
oC
Inrush Rating: 20x (10ms), 1.5x (1min)
Climatic Category: 25/100/21
Hipot Rating: 3000VDC (P/N - E)
Terminals: .250 QD Tabs
Safety Approvals: UR/cCSAus/EN133200
Part Number/Ordering
RP410HP
-X
(Amps)
-Y
(Ycap, nF)
6
0
10
.22
20
.47
1
2.2
4.7
10
22
100
Note: Use any Y (Ycap) with any X (Amps) rating
e.g. RP410HP-20-22
20 Amps with 22nF y-caps
Leakage Current
Ycap, nF
mA, 400V/50HZ
0
0
.22
.004
.47
.009
1
.018
2.2
.04
3.3
.06
4.7
.09
10
.18
22
.4
100
1.8
Schematic
LINE LOAD
RP410HP
High Performance
3PH WYE TO 20A
CHASSIS MOUNT FILTER
ROHS COMPLIANT
RP410HP Series Ultra Compact 3-Phase Wye 1-Stage Power Line
![]() ![]() ![]() Dimensions are shown for reference
only.
RADIUS POWER
www.radiuspower.com
Specifications are subject to
change. Standard & Custom Products PH 714-289-0055
FAX 714-289-2149
6 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
52
75
80
80
70
DM, dB
28
40
47
67
66
10 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
32
60
65
70
67
DM, dB
32
38
44
66
62
20 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
20
38
60
70
75
DM, dB
28
36
44
62
65
A
B
C
MTG HOLE
2.95
2.2
1.57
.2
RP410HP Typical Insertion Loss, 50/50ohm Mechanicals
|